TECHNICAL SPECIFICATIONS
Sizes: 3000VA to 10 000VA

INPUT

VOLTAGE

230V ± 20%

INPUT FREQUENCY RANGE 50Hz ± 5%

OUTPUT

OUTPUT VOLTAGE

230V

OUTPUT WAVEFORM Sinusoidal
NO LOAD TO FULL LOAD 3% Regulation
MAXIMUM TO MINIMUM DC 5% Regulation
CONTINUOUS OVERLOAD 120%
CURRENT LIMITING AT 150 – 200%
OUTPUT FREQUENCY 50Hz Crystal controlled
POWER RATING 0.7 pf

TOTAL HARMONIC DISTORTION

< 4%

CHARGER

VOLTAGE REGULATION

< 1%

A C RIPPLE CONTENT < 0.5%
STANDBY CHARGE C/10 presettable
BOOST CHARGE C/4 presettable

BATTERIES

High quality sealed lead acid, maintenance free batteries ensuring extended life expectancy.

 

EFFICIENCY

90% load dependant

 

ACOUSTIC NOISE

< 50dBA at 1 meter

 

TEMPERATURE RANGE

x 10 to 40° C

 

RFI/EMI

SABS Certified

 

SURGE PROTECTION

Standard

 

ALARMS

VISUAL

AUDIBLE

Mains normal, inverter on,
charger on
Inverter on,
battery low, automatic shutdown



Tel: +27 11 434 1034/5 | Fax: +27 11 434 5707 | Email: ups@matlaups.com